Conventional central 2 zones. Recommended for small fire systems. 2 zones, up to 32 conventional devices can be connected to each zone. 2 monitored relay outputs, 2 monitored alarm outputs, 1 fault signaling relay output. Simple programming from “DIP Switches”. Capacity 2 batteries 12V/5Ah.
In accordance with EN 54-2 and EN 54-4
Manufacturer: UNIPOS
Type: Conventional fire station – 2 zones
Number of zones: 2
Maximum number of detectors per line: 32
Maximum resistance on the line: 100 Ohms
Monitored outputs: 2 – (19-27.5)V DC/1A
Supervised alarm outputs: 2 – (3A/125V AC 3A/30V DC)
Fault signaling outputs: 1 – (3A/125V AC 3A/30V DC)
Control panel: LED (built-in buzzer)
Power supply:
Supply voltage: 220/230V
Frequency: 50Hz
Backup:
Battery type: lead gel
Number of batteries: 2
Battery connection: in series
Nominal battery voltage: 2x12V DC
Battery capacity: 4.5Ah
Backup time without mains voltage: 120 hours (in working mode)
Dimensions: 313x218x85mm
Weight (without batteries): 1500.00
Standards: In accordance with EN 54-2 and EN 54-4
“