Under Regulation CPR – EU no. 305/11
stranded copper wire with the section of 1.0mm2, wire diameter 2.6 mm
Halogen-free, flame resistant, EN50200 certificate (PH120)
Maintain integrity of operation (electrical parameters allowed) in medium flame, E120 (120 minutes in the direct flame).
Loop resistance max. 36 Ω / km at 20 ° C,
The wires: red / black
Operating Temperature -15 ° C to + 80 ° C
nominal operating voltage 200 V
test voltage 2000V (1min / 50Hz)
Insulation resistance min. 200MΩ / km
bending radius approx. 10 x the diameter of the cable
Model / producer ELAN
Nr. yarn: 2
Wire section: 1.0 mm2
Conductor: torsodat in pairs wrapped in fiberglass tape / mica.
Sheath: Halogen free of polymer and flame-retardant halogen free
The wires Red / Black
Conductor diameter: 2.6 mm (copper stranded 30×0.250)