Addressable fixed temperature threshold detector, cf. EN54-5. Insulator included, 2-wire connection, optical signaling indicator, does not require device or addressing settings, protected surface: diameter 10m – height max. 8m, consumption 310?A in standby, 2mA in alarm.
Manufacturer: UNIPOS
Type: Fixed temperature threshold addressable detector
Supply voltage: 15-30VDC
Consumption in working mode: 310 ?A
Consumption in alarm: 2mA
Working mode activation time after powering: up to 40s
Reset type: 5s
Work mode activation time after reset: up to 40s
Temperature class: programmable A1S/A2S (cf: EN54-5:2000) or BS
Protected area: 10m diameter (cf EN54-14)
Max installation height: up to 8 m (cf: EN54-14)
Protection class: IP43
Operating temperature: minus 10 gr. C – plus 55 gr. c
Humidity: (93±3)% at 40 gr. c
Connection: 2 shielded wires
Recommended cable section: (0.8-2.5)mm2
Size (base included): Ø100mm h 47mm
Weight (base included): 100
“